ELECTRICAL INSULATING OILS, ASTM D 3487
In-Service Oils Used in Transformers, Circuit Breakers, and Switching Gear

Recommended Tests

Test Description

Method

Visual Examination of Electrical Insulating Oils

ASTM D 1524

Color, ASTM Color Scale

ASTM D 1500

Interfacial Tension of Oils by Ring Method

ASTM D 971

Viscosity, Kinematic, at 40ºC , cSt

ASTM D 445.a

Dielectric Breakdown Voltage, Disc Electrodes

ASTM D 877

Water Content by Karl Fischer, Insulating Liquids

ASTM D 1533

Dissolved Gasses in Electrical Insulating Oils by Gas Chromatography

ASTM D 3612

Acid Number, Color-Indicator Titration (TAN)

ASTM D 974.a

Corrosive Sulfur in Electrical Insulating Oil

ASTM D 1275

Oxidation Stability, Mineral Insulating Oils, RBOT

ASTM D 2112

 

Additional Optional Tests:

Aniline Point of Petroleum Products

ASTM D 611.a

Dielectric Breakdown Voltage, VDE Electrodes

ASTM D 1816

Dielectric Constant and Power Factor of Electrical Insulating Liquids, 60 Hz, 25 ° C

ASTM D 924

Viscosity, Kinematic, at 100 C, cSt

ASTM D 445.b

Viscosity, Kinematic, at 0 C, cSt

ASTM D 445.c

Oxidation Stability, Mineral Insulating Oil 72 hrs

ASTM D 2440.b

Oxidation Stability, Mineral Insulating Oil 164 hrs

ASTM D 2440.a

Oxidation Inhibitor in Insulating Oil by Infrared Absorption

ASTM D 2668

PCBs in Insulating Oil by Gas Chromatography

ASTM D 4059

PCBs in Transformer Insulating Oils by GC

EPA 600/4-81-045

PCB Content, Screening Test in Oil, ppm

TOL 5049

Sediment and Solid Sludge in Service-Aged Ins Oil

ASTM D 1698

Chloride, Inorganic, and Sulfate in Insulating Oil

ASTM D 878

Sample Containers:

Ultra-clean glass bottles and their mailers, specially designed for lubrication oil analyses, are available to our clients at no charge. These bottles are provided to ensure that results are not affected by potential contamination present in ordinary sample containers.